DFT® Vacuum Breakers provide effective protection against collapse of pressure vessels, tanks and rolls. They prevent condensate "back-up" when equipment is shut down or inlet steam is reduced by modulating control valves. In piping systems, DFT® Vacuum Breakers are used to break siphons, prevent pipe collapse during transient pressure drops, and to provide addition of air on the downstream side of check valves to dampen water hammer.

Click on Column Header to Sort

1 - 13 of 13 | Results Per Page | View | Unit of Measure
1 

Prod. #

Size

Nominal Size (MNPT) A

Unthreaded Inlet Bore B

Cv

Valve Cracking Pressure

Cold Working Pressure

N/A DN 25 1 in N/A 1.00 in N/A 0.56 in14 mm N/A 5.8 N/A 0.60 psi0.041 bar16.7 in.water424 mm.water31.1 mmHg N/A 0 psig2500 psig0 barg172 barg
N/A DN 25 1 in N/A 1.00 in N/A 0.56 in14 mm N/A 5.8 N/A 0.24 psi0.017 bar6.6 in.water167 mm.water12.4 mmHg N/A 0 psig2500 psig0 barg172 barg
N/A DN 40 1.5 in N/A 1.50 in N/A 0.88 in22 mm N/A 13.2 N/A 0.44 psi0.030 bar12.1 in.water307 mm.water22.6 mmHg N/A 0 psig2000 psig0 barg138 barg
N/A DN 50 2 in N/A 2.00 in N/A 1.09 in28 mm N/A 23.1 N/A 0.36 psi0.025 bar10.1 in.water257 mm.water18.8 mmHg N/A 0 psig1500 psig0 barg103 barg
N/A DN 65 2.5 in N/A 2.50 in N/A 1.50 in38 mm N/A 36 N/A 0.16 psi0.011 bar4.5 in.water114 mm.water8.4 mmHg N/A 0 psig850 psig0 barg58.6 barg
N/A DN 80 3 in N/A 3.00 in N/A 1.72 in44 mm N/A 57.4 N/A 0.15 psi0.010 bar4.2 in.water107 mm.water7.8 mmHg N/A 0 psig700 psig0 barg48.3 barg
N/A DN 100 4 in N/A 4.00 in N/A 2.22 in56 mm N/A 90 N/A 0.10 psi0.007 bar2.6 in.water66 mm.water4.8 mmHg N/A 0 psig450 psig0 barg31.0 barg
N/A DN 25 1 in N/A 1.00 in N/A 0.56 in14 mm N/A 5.8 N/A 0.60 psi0.041 bar16.7 in.water424 mm.water31.1 mmHg N/A 0 psig6000 psig0 barg414 barg
N/A DN 40 1.5 in N/A 1.50 in N/A 0.88 in22 mm N/A 13.2 N/A 0.44 psi0.030 bar12.1 in.water307 mm.water22.6 mmHg N/A 0 psig5500 psig0 barg379 barg
N/A DN 50 2 in N/A 2.00 in N/A 1.09 in28 mm N/A 23.1 N/A 0.36 psi0.025 bar10.1 in.water257 mm.water18.8 mmHg N/A 0 psig3000 psig0 barg207 barg
N/A DN 65 2.5 in N/A 2.50 in N/A 1.50 in38 mm N/A 36 N/A 0.16 psi0.011 bar4.5 in.water114 mm.water8.4 mmHg N/A 0 psig1100 psig0 barg75.8 barg
N/A DN 80 3 in N/A 3.00 in N/A 1.72 in44 mm N/A 57.4 N/A 0.15 psi0.010 bar4.2 in.water107 mm.water7.8 mmHg N/A 0 psig900 psig0 barg62.1 barg
N/A DN 100 4 in N/A 4.00 in N/A 2.22 in56 mm N/A 90 N/A 0.10 psi0.007 bar2.6 in.water66 mm.water4.8 mmHg N/A 0 psig450 psig0 barg31.0 barg
1 - 13 of 13 | Results Per Page | View | Unit of Measure
1